Cooper & Hunter 6 Zone 60,000 BTU Ceiling Cassette Mini Split AC R454B 9K+9K+9K+12K+12K+18K
Cooper & Hunter7-Yr WarrantySKU: CH-R60MES-230VO/M09CC+M09CC+M09CC+M12CC+M12CC+M18CC-NO
Product specifications
- Voltage
- 230V
- SEER
- 22.0
- WiFi
- Included
- Zone
- Six Zone
- Type
- Multi-Zone
- Freon
R454B
Choose Your Configuration
Save 10% on these accessories
ARMBRIDGE Mini Split Wall Mounting Bracket High Load Capacity Zinc, Vibration-Absorbing (Up to 550 lbs Each)-10%$49.00
ARMBRIDGE Heavy-Duty Mini Split Ground Stand, Zinc-Coated Brackets for 24,000–60,000 BTU Units Weatherproof Design, 330+ lbs Capacity-10%$89.00
ARMBRIDGE 30 AMP Fusible Metallic Disconnect Box Durable Enclosed Disconnect for Residential and Light Commercial HVAC Systems-10%$29.00
ARMBRIDGE Non-Metallic A/C Whip 3/4" x 6 ft – Pre-Wired Liquid tight Conduit with 8/2 & 10/1 Wires for HVAC & Air Conditioner Power Connection-10%$34.00
FREE Delivery
Ships from the nearest of our three US warehouses, leaves in 1–2 business days. Shipping policy
COOPER & HUNTER · MULTI-ZONE
Built for year-round comfort
CH-R60MES-230VO/M09CC+M09CC+M09CC+M12CC+M12CC+M18CC-NO
System Specs
| Cooling Capacity | 60,000 BTU/h |
|---|---|
| Heating Capacity | 60,000 BTU/h |
| SEER2 | 22 |
| EER2 | 10 |
| Voltage | 230V |
| Refrigerant | R454B |
|---|---|
| Compressor | Inverter |
| Climate Range | -13–122°F / -13–75°F outdoor ambient |
| Sound Level (indoor) | 40/37.5/26 dB |
| Warranty | 7-Yr Compressor |
Indoor Unit Specs
| Unit Dimensions (WxDxH) | Net / Gross Weight | Remote Control |
|---|---|---|
| 22.44 × 22.44 × 9.65 in | 35.27 / 41.89 lb | Wire controller + remote controller available |
Product Description
The Cooper & Hunter 6-Zone Mini Split System features 6 ceiling cassette zones rated at 9,000 Btu/h, 9,000 Btu/h, 9,000 Btu/h, 12,000 Btu/h, 12,000 Btu/h, and 18,000 Btu/h, paired with an outdoor unit rated for 60,000 BTU nominal cooling and capable of operation down to -13°F ambient temperature. It uses R454B refrigerant and achieves a SEER2 efficiency rating of 22.
6 Modes for Maximum Comfort
Engineered to adapt to every season, every room, every need.
Maintain a comfortable indoor temperature by automatically switching between heating and cooling as needed. Ideal for year-round use.
WHEREVER YOU ARE
Control your comfort, your way
- Easy scheduling & timer
- Multiple ways to control your comfort
- Smart geo location
- In-app support & assistance
- Voice control

IN THE BOX
Everything included with this system
- Cooper & Hunter MES 60,000 BTU Outdoor Condenser, 230V, R454B - Mini Split Air Conditioner Heat Pump
- Indoor Multi-Zone — CH-RH09MCT × 3
- Indoor Multi-Zone — CH-RH12MCT × 2
- Indoor Multi-Zone — CH-RH18MCT
WARRANTY
BACKED BY COOPER & HUNTER
Industry-leading protection on every unit
Compressor: 7-year coverage
With product registration after professional installation.
Parts & components: 5-year coverage
All major components and refrigerant circuit parts.
Technical Specifications
Outdoor Unit Specs— CH-R60MES-230VO
| Model | CH-R60MES-230VO |
|---|---|
| Unit Dimensions (WxDxH) | 37.48 x 16.34 x 52.48 in |
| Net/Gross Weight | 237.88/270.28 lb |
| Packing Dimensions (WxDxH) | 43.11 x 19.49 x 58.27 in |
| Power Supply | 208-230V, 1Ph, 60Hz |
| Maximum Fuse Size | 40 A |
| Min. Circuit Ampacity | 36 A |
| Copper Line Size (Liquid/Gas) | 6x1/4" - 4x3/8"+2x1/2" |
| Noise Level | 65 dB |
| Airflow | 4,502.8 CFM |
| Dehumidification | 10.57 pt/h |
Indoor Unit Specs
| Model | CH-RH09MCT | CH-RH12MCT | CH-RH18MCT |
|---|---|---|---|
| Unit Dimensions (WxDxH) | 22.44 x 22.44 x 9.65 in | 22.44 x 22.44 x 9.65 in | 22.44 x 22.44 x 9.65 in |
| Net/Gross Weight | 35.27/41.89 lb | 35.27/41.89 lb | 35.27/41.89 lb |
| Packing Dimensions (WxDxH) | 28.15 x 25.20 x 11.61 in | 28.15 x 25.20 x 11.61 in | 28.15 x 25.20 x 11.61 in |
| Power Supply | 208-230V, 1Ph, 60Hz | 208-230V, 1Ph, 60Hz | 208-230V, 1Ph, 60Hz |
| Maximum Fuse Size | 15 A | 15 A | 15 A |
| Min. Circuit Ampacity | 3 A | 3 A | 3 A |
| Copper Line Size (Liquid/Gas) | 1/4"/3/8" | 1/4"/3/8" | 1/4"/1/2" |
| Noise Level (Hi/Med/Lo) | 40/37.5/26 dB | 43.5/40.5/27.5 dB | 44.5/41/27.5 dB |
| Dehumidification | 1.86 pt/h | 3.07 pt/h | 4.23 pt/h |
| Drain Pipe Diameter | 1" | 1" | 1" |
| Controller | wire controller + remote controller available | wire controller + remote controller available | wire controller + remote controller available |
System Specs
| Cooling — Rated Capacity (Range) | 60,000 Btu/h (19,000–62,000) |
|---|---|
| Heating at 47°F — Rated Capacity (Range) | 60,000 Btu/h (20,000–60,000) |
| Rated Heating at 5°F | 39,000 Btu/h |
| SEER2 / EER2 | 22 / 10 |
| HSPF4 / HSPF5 / COP (47°F) | 9.5 / 7.4 / 3.7 |
| Outdoor Unit MCA / Max. Fuse | 36 A / 40 A |
| Max. Connectable Indoor Units | 6 |
| Outdoor Noise Level | 65 dB(A) |
| Outdoor Unit Dimensions (W×D×H) | 37.48 × 16.34 × 52.48 in |
| Outdoor Unit Net / Gross Weight | 237.88 / 270.28 lbs |
| Refrigerant Type / Charge | R454B / 151.68 oz |
| Pre-charged Line Length | 150 ft (add 0.16 oz/ft for 1/4 in liquid pipe / 0.32 oz/ft for 3/8 in liquid pipe) |
| Max. Total Pipe Length / Max. to One Indoor | 262.4 ft / 114.8 ft |
| Max. Height Difference (Indoor–Outdoor / Between Indoors) | 49.2 ft / 33 ft |
| Operating Range — Cooling / Heating | -13–122°F / -13–75°F outdoor ambient |
Series Comparison Table
Technical specifications for every model in the series — this product is one of them.
System Type
| Specification | Hyper | Regular |
|---|---|---|
| Ceiling Cassette PRO | CH-RSH09-12MCT(Dip Switch for 9K) | CH-RSH09-12MCT(Dip Switch for 12K) |
| Ceiling Cassette | CH-RH09MCT | CH-RH12MCT |
| Panel Model Number | CH-NPNL09-18CT | CH-NPNL09-18CT |
| Power Supply (V,Ph,Hz) | 208/230,1,60 | 208/230,1,60 |
| Rated Capacity (Btu/h) | 9,000 | 12,000 |
| Minimum Circuit Ampacity (A) | 3 | 3 |
| Max. Fuse (A) | 15 | 15 |
| Indoor Air Flow - Turbo/Hi/Mi/Lo (CFM) | 417.9/364.9/306.1/194.2/147.2 | 417.9/364.9/306.1/194.2/147.2 |
| Indoor Noise Level - Hi/Mi/Lo (dB(A)) | 42.5/40/37.5/26/24 | 46/43.5/40.5/27.5/26 |
| Dimension (WxDxH) (inch) | 22.44x22.44x9.65 | 22.44x22.44x9.65 |
| Packing (WxDxH) (inch) | 28.15x25.20x11.61 | 28.15x25.20x11.61 |
| Net/Gross Weight (lbs.) | 35.27/41.89 | 35.27/41.89 |
| Cooling (°F) | 60~90 | 60~90 |
| Heating (°F) | 32~86 | 32~86 |
Outdoor Regular
| Specification | CH-R60MES-230VOThis model | CH-R18MES-230VO | CH-R28MES-230VO | CH-R36MES-230VO | CH-R48MES-230VO |
|---|---|---|---|---|---|
| Power Supply (V, Ph, Hz) | 208/230, 1, 60 | 208/230, 1, 60 | 208/230, 1, 60 | 208/230, 1, 60 | 208/230, 1, 60 |
| Voltage Range (V) | 187-253 | 187-253 | 187-253 | 187-253 | 187-253 |
| Cooling Rated Capacity (range) (Btu/h) | 19,000~62,000 | 5,400~21,600 | 7,200~32,000 | 9,000~42,000 | 12,000~55,000 |
| Cooling Rated Current (A) | 26.2 | 6 | 9.2 | 13.5 | 16.6 |
| EER2 | 10 | 14 | 13 | 12 | 12.5 |
| SEER2 | 22 | 25.1 | 25 | 24 | 24 |
| Heating Rated Capacity (range) (Btu/h) | 20,000~60,000 | 5,700~21,600 | 8,400~29,000 | 10,000~42,500 | 13,000~53,000 |
| Heating Rated Current (A) | 21 | 6.8 | 9.2 | 14 | 16.3 |
| Heating at 47°F COP (W/W) | 3.7 | 3.8 | 3.8 | 3.5 | 3.8 |
| HSPF4 | 9.5 | 9.8 | 9.5 | 9.5 | 10.3 |
| HSPF5 | 7.4 | 7.8 | 7 | 7 | 8 |
| Heating at 5°F Rated Capacity (Btu/h) | 39,000 | 13,500 | 19,000 | 26,000 | 36,000 |
| Minimum Circuit Ampacity (Outdoor unit) (A) | 40 | 16 | 23 | 30.5 | 40 |
| Max. Fuse (Outdoor unit) (A) | 45 | 20 | 25 | 35 | 45 |
| Outdoor Air Flow (Max) (CFM) | 4,502.8 | 1,765.8 | 2,130.7 | 2,148.4 | 4,502.8 |
| Outdoor Noise Level (Sound Pressure) (dB(A)) | 65 | 59.5 | 61 | 64.5 | 63 |
| Dimension (W×D×H) (inch) | 37.48x16.34x52.48 | 35.04x13.46x26.50 | 37.24x16.14x31.89 | 37.24x16.14x31.89 | 37.48x16.34x52.48 |
| Packing (W×D×H) (inch) | 43.11x19.49x58.27 | 40.55x17.24x29.53 | 42.91x19.68x34.84 | 42.91x19.68x34.84 | 43.11x19.49x58.27 |
| Net/Gross Weight (lbs) | 237.88/270.28 | 100.53/109.35 | 138.89/149.69 | 168.87/180.12 | 222.00/254.19 |
| Refrigerant Type/Charged (oz) | R454B/151.68 | R454B/61.73 | R454B/84.66 | R454B/120.63 | R454B/148.15 |
| Refrigerant Precharge (ft) | 150 | 75 | 100 | 125 | 150 |
| Additional Charge for Each (0.16 for 1/4 in liquid pipe / *0.32 for 3/8 in liquid pipe) (oz/ft) | 0.16 / 0.32 | 0.16 / 0.32 | 0.16 / 0.32 | 0.16 / 0.32 | 0.16 / 0.32 |
| Design Pressure (PSIG) | 550/340 | 550/340 | 550/340 | 550/340 | 550/340 |
| Refrigerant Piping Liquid Side (inch) | 6 x 1/4" | 3 x 1/4" | 4 x 1/4" | 5 x 1/4" | 6 x 1/4" |
| Refrigerant Piping Gas Side (inch) | 4 x 3/8" + 2 x 1/2" | 3 x 3/8" | 3 x 3/8" + 1 x 1/2" | 4 x 3/8" + 1 x 1/2" | 4 x 3/8" + 2 x 1/2" |
| Max. Pipe Length (ft) | 262.4 | 196.8 | 262.4 | 262.4 | 262.4 |
| Max. Length for One Indoor Unit (ft) | 114.8 | 98.4 | 114.8 | 114.8 | 114.8 |
| Max. Height Difference in Level (ft) | 49.2 | 49.2 | 49.2 | 49.2 | 49.2 |
| Max. Height Difference Between Indoor Units (ft) | 33 | 33 | 33 | 33 | 33 |
| Ambient Temperature Cooling (°F) | -13~122 | -13~122 | -13~122 | -13~122 | -13~122 |
| Ambient Temperature Heating (°F) | -13~75 | -13~75 | -13~75 | -13~75 | -13~75 |
| Certification: AHRI | ✔ | ✔ | ✔ | ✔ | ✔ |
| Certification: Energy Star | ✔ | ✔ | ✔ | ✔ | ✔ |
| Certification: NEEP | ✔ | ✔ | ✔ | ✔ | ✔ |
| Certification: ETL | ✔ | ✔ | ✔ | ✔ | ✔ |
Outdoor Hyper
| Specification | CH-RVHP19M-230VO | CH-RVHP28M-230VO | CH-RVHP36M-230VO | CH-RVHP48M-230VO | CH-RVHP55M-230VO |
|---|---|---|---|---|---|
| Power Supply (V/Ph/Hz) | 208/230, 1, 60 | 208/230, 1, 60 | 208/230, 1, 60 | 208/230, 1, 60 | 208/230, 1, 60 |
| Operating Range (V) | 187-253 | 187-253 | 187-253 | 187-253 | 187-253 |
| Cooling Capacity (BTU/h) | 5,400~28,000 | 7,200~37,000 | 9,000~43,000 | 12,000~57,000 | 19,000~59,000 |
| SEER2 | 5.6 | 9.5 | 12 | 17.3 | 18.5 |
| EER | 15 | 12.5 | 13 | 12 | 12 |
| IEER | 25 | 23 | 23 | 23 | 22.2 |
| Heating Capacity (BTU/h) | 5,700~27,000 | 8,400~36,000 | 10,000~44,000 | 13,000~57,000 | 20,000~59,000 |
| HSPF2 | 6.5 | 9.1 | 11.5 | 17.3 | 20.1 |
| COP | 4 | 3.8 | 4 | 3.7 | 3.5 |
| SCOP | 10.4 | 10.5 | 10.7 | 11 | 10.5 |
| Power Input (W) | 8.5 | 8.5 | 8.5 | 9 | 8.5 |
| Air Flow (CFM) | 19,000 | 27,000 | 36,000 | 47,000 | 47,000 |
| Sound Level Indoor (dBA) | 17.5 | 30 | 37 | 37 | 39.5 |
| Sound Level Outdoor (dBA) | 20 | 35 | 40 | 40 | 40 |
| Weight Indoor (lbs) | 2,130.7 | 2,148.4 | 3,037.2 | 4,502.8 | 4,502.8 |
| Weight Outdoor (lbs) | 61.5 | 61 | 65 | 65 | 65 |
| Dimensions Indoor (in) | 37.24x16.14x31.89 | 37.24x16.14x31.89 | 38.58x16.34x38.39 | 37.48x16.34x52.48 | 37.48x16.34x52.48 |
| Dimensions Outdoor (in) | 42.91x19.68x34.84 | 42.91x19.68x34.84 | 45.08x19.68x42.52 | 43.11x19.49x58.27 | 43.11x19.49x58.27 |
| Shipping Weight Indoor/Outdoor (lbs) | 137.35/148.15 | 168.43/179.67 | 211.86/244.71 | 246.47/276.68 | 246.47/276.68 |
| Refrigerant Type/Amount (lbs) | R454B/78.31 | R454B/120.63 | R454B/134.04 | R454B/151.68 | R454B/151.68 |
| Fuse Size (A) | 75 | 100 | 125 | 150 | 150 |
| Wire Size (AWG) | 0.16 / 0.32 | 0.16 / 0.32 | 0.16 / 0.32 | 0.16 / 0.32 | 0.16 / 0.32 |
| Control Voltage (V) | 550/340 | 550/340 | 550/340 | 550/340 | 550/340 |
| Liquid Line | 3 x 1/4" | 4 x 1/4" | 5 x 1/4" | 6 x 1/4" | 6 x 1/4" |
| Suction Line | 3 x 3/8" | 3 x 3/8" + 1 x 1/2" | 3 x 3/8" + 2 x 1/2" | 4 x 3/8" + 2 x 1/2" | 4 x 3/8" + 2 x 1/2" |
| Max Line Length (ft) | 196.8 | 262.4 | 262.4 | 262.4 | 262.4 |
| Max Elevation Diff (ft) | 98.4 | 114.8 | 114.8 | 114.8 | 114.8 |
| Max Head Pressure (ft) | 49.2 | 49.2 | 49.2 | 49.2 | 49.2 |
| Max Suction Pressure (ft) | 33 | 33 | 33 | 33 | 33 |
| Operating Range Cooling (°F) | -22~122 | -22~122 | -22~122 | -22~122 | -22~122 |
| Operating Range Heating (°F) | -22~75 | -22~75 | -22~75 | -22~75 | -22~75 |
| Feature 1 | ✓ | ✓ | ✓ | ✓ | ✓ |
| Feature 2 | ✓ | ✓ | ✓ | ✓ | ✓ |
| Feature 3 | ✓ | ✓ | ✓ | ✓ | ✓ |
| Feature 4 | ✓ | ✓ | ✓ | ✓ | ✓ |
Which system is right for you?
| Your selection | ||||
|---|---|---|---|---|
| Cooling Capacity | 60,000 BTU/h | 60,000 BTU/h | 60,000 BTU/h | 60,000 BTU/h |
| SEER2 Rating | 22.0 | 22.0 | 22.0 | 22.0 |
| Refrigerant | R454B | R454B | R454B | R454B |
| Zones | Six Zone | Dual Zone | Three Zone | Four Zone |
| Voltage | 230V | 230V | 230V | 230V |
| Shop Now → | Shop Now → | Shop Now → |
Frequently asked questions.
How many rooms can the Cooper & Hunter 6 Zone 60,000 BTU mini split cool?
The Cooper & Hunter 6 Zone mini split can effectively cool up to six rooms, providing a total coverage of approximately 2,500 sq ft. Each zone can be independently controlled, allowing for tailored comfort in each space.
Can I mix BTU sizes for different zones in the Cooper & Hunter system?
Yes, you can mix BTU sizes in the Cooper & Hunter 6 Zone system. For instance, the unit includes 9K, 12K, and 18K configurations, allowing you to customize the cooling capacity based on the specific needs of each room.
Do all zones run simultaneously with the Cooper & Hunter mini split?
No, all zones do not need to run simultaneously in the Cooper & Hunter system. You can operate each zone independently, which can save energy and costs when certain areas do not require cooling.
Is the Cooper & Hunter 60,000 BTU mini split efficient compared to multiple single-zone units?
The Cooper & Hunter 60,000 BTU mini split boasts a high efficiency rating of 22.0 SEER, making it more energy-efficient compared to multiple single-zone units. This efficiency translates to lower energy bills and a reduced carbon footprint.
What is the warranty for the Cooper & Hunter 6 Zone mini split system?
The Cooper & Hunter 6 Zone mini split comes with a comprehensive warranty that includes a 5-year parts warranty and a 7-year compressor warranty, provided you register the unit within 30 days of purchase.
Does the Cooper & Hunter mini split come pre-charged with refrigerant?
Yes, the Cooper & Hunter 6 Zone mini split system comes pre-charged with R454B refrigerant for up to 25 ft of line set. This feature simplifies installation and ensures optimal performance right out of the box.
Manufacturer Technical Support
Reach your brand's tech support team directly
You may also like
- R454BSEER2 21.6HEATS down to −22°FCOOLS up to 122°F
7-Yr Warranty
Cooper & HunterCooper & Hunter Hyper Heat 9,000 BTU Single Zone Ceiling Cassette, 230V, R454B - Ductless Mini Split Air Conditioner Heat PumpFree Shipping
- R32SEER2 22.0Heats & Cools
7-Yr Warranty
BravoBravo Pisa 12,000 BTU Single Zone Ceiling Cassette, 230V, R32 - Ductless Mini Split Heat PumpFree Shipping
- R454BSEER2 21.1HEATS down to −13°FCOOLS up to 122°F
7-Yr Warranty
Cooper & HunterCooper & Hunter 12,000 BTU Single Zone Ceiling Cassette, 230V, R454B - Ductless Mini Split Air Conditioner Heat PumpFree Shipping
- R32SEER2 22.0HEATS down to −13°FCOOLS up to 126°F
7-Yr Warranty
Bravo2 zone 18,000 BTU BRAVO Ductless Mini Split AC Ceiling Cassette 9k+9kFree Shipping
The Cooper & Hunter 6-Zone Mini Split System features 6 ceiling cassette zones rated at 9,000 Btu/h, 9,000 Btu/h, 9,000 Btu/h, 12,000 Btu/h, 12,000 Btu/h, and 18,000 Btu/h, paired with an outdoor unit rated for 60,000 BTU nominal cooling and capable of operation down to -13°F ambient temperature. It uses R454B refrigerant and achieves a SEER2 efficiency rating of 22.
Key Features
- 6-zone system — the CH-R60MES-230VO outdoor unit supports up to 6 indoor units, each individually controlled; port adapters included, no branch boxes required
- 60,000 Btu/h rated cooling / 60,000 Btu/h rated heating — inverter range 19,000–62,000 cooling, 20,000–60,000 heating (Btu/h)
- 22 SEER2 / 10 EER2 / 9.5 HSPF4 — current R454B-generation efficiency
- Heats down to -13°F outdoor ambient — 39,000 Btu/h rated heating at 5°F; cooling operation -13–122°F
- ETL listed, AHRI certified, Energy Star Cold Climate & NEEP listed